This emergency lighting module is designed to convert a wide range of LED types, and is an ideal choice for converting most standard LED luminaires and arrays containing from 3 to 20 (60V) LEDs in series. This unit is designed to utilize the existing LED driver and panel layout (no need to break into the LED circuit) to be dimmed to 3W in case of emergency. The driver can automatically adjust the output LED current and provide the optimum match between the battery and the load, which enables maximum illumination whilst ensuring full battery duration. The driver is compatible with a wide range of LEDs such as Philips Fortimo DLM, SLM and LLM ranges, Bridgelux LS/ES/RS ranges, Citizen 4-41W ranges, GE Infusion, Xicato and many others.
Some of the product highlights include :
Mains voltage | 220~240VAC |
Mains frequency | 50/60Hz |
Mains power | 4W |
Mains current | 16mA - 18mA |
Output voltage (U-out Max.) | 70VDC |
Output LED Current | [ 40mA ,60 VDC | 300mA ,9 VDC] |
Power Factor | 0.75 |
Operation Temperature | Ta:0~+50℃ |
Battery charge voltage | 3V~4.3V |
Battery charge current | 200mA (Max.) |
Battery pack | [ BPC10| BPC11 | BPC15 | BPC16 ] |
Charge period | 24 hours |
Max. case temp. | 75℃ |
Battery duration | Min. 3 hours |
Mains Switch-over voltage range | 155VAC~180VAC |
Over-heat Protection | Over-heat protection with auto-reset |
Dielectric Strength | Input to output: 1750VAC |
EMC Standard | EN55015:2007 version EN61547 |
Safety Standard | EN50172 | EN61347-2-7 | EN61347-2-13 | IEC62034 | BS5266 |
IP Grade | IP20 |
Certifications | Semko, CB, CE , EMC |